Aric wrote:
> Anyway, since I'll have to run the electric through a trench, I was
wondering what else might be useful to put in
> there before its covered up. My thoughts are (aside from the 60 amp 220
service and a sub panel in the
> garage):
> 1. A 3/4" or so conduit for pulling phone, network and coax (or anything
else low voltage)
Check your local codes. Around here low-voltage lines such as these have to
be something like 12" or 18" away from the electrical service lines, even
with the service in conduit.
Harry Phinney